Skip to main content

Table 1 DC link voltages and group no.

From: Equivalent modeling of PMSG-based wind power plants considering LVRT capabilities: electromechanical transients in power systems

PMSG

P (MW)

Calculated result (pu)

Simulated result (pu)

Group no. based on calculated result

Group no. based on simulated result

PMSG

P (MW)

Calculated result (pu)

Simulated result (pu)

Group no. based on calculated result

Group no. based on simulated result

1

0.25

0.9476

0.9944

3

3

16

1.27

1.0837

1.0842

1

1

2

0.58

1.0003

1.0076

2

2

17

0.86

1.0158

1.0222

2

2

3

0.35

0.9539

0.9944

3

3

18

0.52

0.9617

0.9902

3

3

4

1.06

1.0710

1.0713

1

1

19

0.56

0.9662

0.9882

3

3

5

1.47

1.1322

1.1306

1

1

20

0.68

0.9857

0.9980

3

3

6

1.88

1.1911

1.1887

1

1

21

0.94

1.0293

1.0342

2

2

7

1.83

1.1831

1.1807

1

1

22

0.82

0.9962

1.0039

3

2

8

1.65

1.1877

1.1844

1

1

23

0.72

0.9771

0.9919

3

3

9

1.03

1.0923

1.0910

1

1

24

1.00

1.0245

1.0304

2

2

10

1.93

1.2245

1.2209

1

1

25

1.25

1.0519

1.0552

2

2

11

0.43

0.9593

0.9925

3

3

26

0.54

0.9244

0.9958

3

3

12

0.32

0.9335

0.9948

3

3

27

0.80

0.9688

0.9887

3

3

13

0.14

0.8948

0.9954

3

3

28

0.98

1.0009

1.0086

2

2

14

0.72

1.0012

1.0070

2

2

29

1.01

1.0048

1.0117

2

2

15

0.91

1.0267

1.0316

2

2

30

1.56

1.0914

1.0924

1

1