Table 6 Response of protection scheme for phase(s) to ground faults with Rf = 5 Ω and phase(s) to phase fault cases, with Rf = 0 Ω at different fault inception angles

From: An improved fault detection classification and location scheme based on wavelet transform and artificial neural network for six phase transmission line using single end data only

Fault type

Inception angle (Φi) in degree

La (actual location) in km

Output of proposed classifier

Relay operation time (ms)

Lf (estimated location) in km

Error (%)

a

b

c

d

e

f

g

dg

25°

34

0

0

0

1

0

0

1

9.163

33.939

−0.089

bcg

50°

34

0

1

1

0

0

0

1

12.495

34.459

0.675

bcdg

75°

34

0

1

1

1

0

0

1

9.163

33.907

−0.137

acefg

100°

34

1

0

1

0

1

1

1

7.497

34.121

0.178

abcefg

125°

34

1

1

1

0

1

1

1

9.996

33.664

−0.494

abcdefg

200°

34

1

1

1

1

1

1

1

8.330

34.305

0.449

ab

240°

34

1

1

0

0

0

0

0

9.996

33.608

−0.576

abc

260°

34

1

1

1

0

0

0

0

9.996

33.713

−0.422

abef

280°

34

1

1

0

0

1

1

0

7.497

33.635

−0.537

abdef

310°

34

1

1

0

1

1

1

0

9.163

34.435

0.639

abcdef

360°

34

1

0.99

1

1

1

1

0

7.497

34.421

0.619