Skip to main content

Table 4 Response of protection scheme for faults at different location

From: An improved fault detection classification and location scheme based on wavelet transform and artificial neural network for six phase transmission line using single end data only

Fault type

La (actual location) in km

Output of classifier

Relay operation time (ms)

Lf (estimated location) in km

Error (%)

a

b

c

d

e

f

g

e.g.

4

0

0

0

0

1

0

1

9.163

3.729

−0.399

afg

9

1

0

0

0

0

1

1

7.497

9.217

0.319

adfg

14

1

0

0

1

0

1

1

7.497

13.533

−0.688

abdeg

19

1

1

0

1

1

0

1

7.497

19.139

0.204

abcdfg

24

1

1

1

1

0

1

1

7.497

24.373

0.548

abcdefg

32

1

1

1

1

1

1

1

8.330

32.135

0.199

de

36

0

0

0

1

1

0

0

12.495

36.404

0.594

abe

41

1

0.99

0

0

0.99

0

0

9.996

41.301

0.443

abce

52

1

1

1

0

1

0

0

9.996

51.990

−0.015

acdef

58

1

0

1

1

1

1

0

9.163

57.618

−0.562

abcdef

64

1

0.99

1

1

1

1

0

9.163

63.979

−0.031