Table 2 Response of protection scheme for close-in phase(s) to ground faults with Φi = 0º, Rf = 5 Ω and remote phase(s) to phase fault with Φi = 0º, Rf = 0 Ω

From: An improved fault detection classification and location scheme based on wavelet transform and artificial neural network for six phase transmission line using single end data only

Fault type

La (actual location) in km

Output of classifier

Relay operation time (ms)

Lf (estimated location) in km

Error (%)

a

b

c

d

e

f

g

ag

1

1

0

0

0

0

0

1

9.163

0.801

−0.293

bfg

2

0

1

0

0

0

1

1

9.163

2.018

0.026

abcg

1

1

1

1

0

0

0

1

9.996

0.801

−0.293

abcdg

2

1

1

1

1

0

0

1

9.996

2.192

0.282

abcefg

1

1

1

1

0

1

1

1

9.996

0.805

−0.287

abcdefg

2

1

1

1

1

1

1

1

9.996

1.979

−0.031

ab

1

1

1

0

0

0

0

0

12.495

0.801

−0.293

acd

2

1

0

1

1

0

0

0

9.163

2.062

0.091

abcf

1

1

1

1

0

0

1

0

11.662

0.822

−0.262

abcdf

2

1

1

1

1

0

1

0

8.330

1.994

−0.008

abcdef

1

1

1

1

1

1

1

0

11.662

0.828

−0.253